Campus Oulu
Site address: Kaapelitie 4, 906200 Oulu, Finland
Campus Oulu complements our Oulu data center cluster with its capacity to host high-density workloads. The campus is being built in phases, with capacity up to 300MW.
Network, power and cooling are engineered to meet demanding high-density workloads, the Campus supports NVIDIA GB300 NVL72 already and ready for Vera Rubin. Or you can let us know your specifications. For sustainable performance, the data center operates on 100% renewable energy.
Power
Total power capacity
up to 300MW
Max rack density
120-250 KW
UPS redundancy
N+1 / 2N *
Backup power type
Generator
Backup power redundancy
N+1 / 2N *
PUE
1.2
*can be modified according to customer needs
Cooling
Temperature
20–26°C
Humidity
30–70%
Cooling redundancy
N+1
Fire prevention & suppression
Detection system
High sensitivity smoke detection system (VESDA)
Gas suppression
gas fire suppresion system, availability for sprinklers
Security
Bullet proof glass checkpoint
No
Mantrap
optional
CCTV
Yes (6 month retention)
Security guards
On call
Onsite personnel 24/7
No
Biometric
yes
Burglar resistance
Not specified
Authentication factors
Access card, PIN, retinal scan
Amenities
Meeting rooms
Yes
Break rooms
Yes
Onsite car parking
Yes
Spare parts
Yes
Staging room
Yes
Office space
Yes
WiFi access
Yes
Remote hands 24/7
Yes
Remote eyes 24/7
Yes
Services
Colocation
Yes
GPU hosting
Yes
Dedicated servers
Yes
VPS
No
Managed hosting
Yes
Extended SLA
Yes
Network services
Yes
Remote hands
Yes
Remote eyes
Yes
Colocation
Suites/Cages
No
Sub-racks
No
Rack height
42U
Rack width/depth
800 x 1200 mm
Rack mounted PDU
Modular
Communication entry points
2
Meet-me rooms
2
Fiber patch panel
Yes
Copper patch panel
No
Network connectivity
Provider / exchange
ASN
Dark fibre
Internet exchange
Wavelength
IP transit
Internet
Ethernet transport
Elisa
–
✓
–
–
–
–
–
Telia Finland
–
✓
–
–
–
–
–
DNA Oy
–
✓
–
–
–
–
–
Glesys
–
✓
–
–
–
–
–
Building
Nearest airport
21 km
Loading docks
Yes
Purpose-built DC
No
Gross colocation space
3500 m²
Floor load capacity
2000 kg/m2*
*adjustable per requirements
Sustainability
Renewable electricity supply
100% renewable electricity
Heat recovery
in planning
Generator fuel type
HVO
Last updated
Was this helpful?